The rule of thumb: twice the output.
Allow for twice the boiler's output in cubic metres of wood chips per year – and up to three times with poorer chips.
With poorer chipsup to 300 m³
200 m³Wood chips
51 m³Pellets
Pellets take up less space: divide the chip volume by 3.9 to get the approximate volume of pellets.
Fuel use from 50 to 1,000 kW.
| Boiler output | Wood chips per year | With poorer chips | Pellets per year |
|---|---|---|---|
| 50 kW | 100 m³ | 150 m³ | 26 m³ |
| 100 kW | 200 m³ | 300 m³ | 51 m³ |
| 200 kW | 400 m³ | 600 m³ | 103 m³ |
| 500 kW | 1,000 m³ | 1,500 m³ | 256 m³ |
| 1,000 kW | 2,000 m³ | 3,000 m³ | 513 m³ |
Calculated with the rule of thumb; approximate volumes. We work out your consumption in the heat-load calculation.
What affects fuel use.
- The quality and moisture content of the chips. Wetter wood chips mean lower output and higher consumption – hence up to three times the output with poorer chips.
- The heating demand. The buildings, how cold the winters are and whether the heat also goes to hot water, drying or processes.
- Operation. An accumulator tank means fewer starts and stops and more even combustion.
From fuel use to fuel store.
Fuel use determines how big the store needs to be and how often it needs filling. A spring agitator holds up to 180 m³ and a scraper-floor store up to 500 m³. A pellet silo holds 11–185 m³.